Tower capability: where the demand curve meets the characteristic
The demand curve against the tower characteristic, and the crossing a capability figure is built from.
The design-condition demand curve — the Merkel integral evaluated across L/G — against the tower’s characteristic KaV/L = C (L/G)^m, and their crossing, which is what a capability figure is built from.
Reference conditions: cold water 32 °C, hot water 42 °C, entering air 33 °C dry bulb / 27 °C wet bulb, cp,w 4.18 kJ/kg·K, fill exponent m = −0.60 (illustrative); the crossing falls at L/G 1.42 against a design L/G of 1.50, giving 94.7 %.
Formula: KaV/L = ∫ cp,w dTw / (hs(Tw) − ha(Tw)) against KaV/L = C (L/G)^m, with C = Mtest / (L/Gtest)^m and Capability % = 100 × (L/G)cap / (L/G)design.
Sources
- Kloppers & Kröger — Cooling tower performance: a critical evaluation of the Merkel assumptions (SAIMechE, 2004) — the Merkel formulation behind the demand curve, the operating line, and the Lewis-factor assumption this article lists.
- Hensley, J.C. (ed.) — Cooling Tower Fundamentals, 2nd edition (SPX Cooling Technologies, 2009) — the demand-versus-characteristic comparison, and the acceptance code’s alternative capability method that uses the characteristic curve.
- ASHRAE Handbook—Fundamentals (2025 edition) — Psychrometrics — the moist-air relations the saturated-air enthalpy
hs(Tw)of this article’s chart is computed from. - Buck Research Instruments — CR-1A User’s Manual, Appendix 1: Humidity Conversion Equations (revised 7/96) — the saturation vapour pressure over water that the chart evaluates.
- CTI ATC-105 — Acceptance Test Code for Water Cooling Towers — the Cooling Technology Institute’s acceptance test code for water cooling towers, referenced by this article’s statement that a capability result is only defensible when produced under it; the procedure is not reproduced here.
Guide: Cooling Tower Capability Explained: What 100% Really Means