Range and Approach: the two spans that set a cooling tower's duty
A worked Range and Approach ladder with the effectiveness curve, and the formulas behind both spans.
The three temperatures of one example — entering wet bulb, cold water and hot water — as a ladder, with Range and Approach drawn as the spans between them; below it, the cooling effectiveness R ÷ (R + A) against Range, with the example marked on its curve.
Reference conditions: entering wet bulb 27.00 °C, cold water 31.00 °C, hot water 37.00 °C — Range 6.00 °C, Approach 4.00 °C, effectiveness 60.00 %.
Illustrative, computed from the definitions above — not a measurement. The ladder carries the example’s three temperatures and the two spans between them; the curve is the same effectiveness relation with Approach held at the example’s own 4.00 °C.