Cooling Tower Cleaning and Comparative Performance Test

A service report documents cooling-tower cleaning followed by comparative thermal and airflow tests on Cell A.

Before and after

ParameterBefore · 10 Aug 2024After · 19 Oct 2024
Water flow171.60 m³/h208.70 m³/h
Hot water31.00°C31.00°C
Cold water29.50°C28.10°C
Wet bulb27.00°C25.60°C
Cooling effectiveness37.50%53.70%
Airflow30.82 m³/s32.98 m³/s
Fan power9.48 kW9.48 kW

The report records an effectiveness increase of 16.2 percentage points after cleaning the fill pack and drift eliminators.

Test limitation

The service report also states that these effectiveness calculations are not a substitute for a full CTI capability assessment. Several measured conditions were outside the recommended ATC-105 variation limits, including water flow, cooling range and fan driver power.

That caveat should remain visible in any public case study: the data demonstrates a comparative change between the two field tests, not certified design capability.