Cooling Tower Glossary
Eleven components of a typical induced-draft counterflow cooling tower, from the fan stack and drive train down to the cold water basin — the same definitions used in the interactive tower explorer on our homepage.
Fan stack
Shell
Velocity-recovery stack. The bell-mouth inlet turns the air into the fan without separation, and the flared exit converts discharge velocity back into static pressure — a surprising share of fan energy is won or lost in this profile alone.
See also:
Fan blade
Drive train
Axial fan, 4–6 blades, from roughly 2.5 to 40 ft in diameter depending on cell size. Blade pitch is the primary airflow adjustment, and low-noise profiles exist where a site needs them.
See also:
Gearbox
Drive train
Right-angle bevel gearbox. Turns the horizontal drive into the vertical fan shaft. Oil level, backlash and bearing wear are the routine inspection points.
See also:
Motor
Drive train
Totally-enclosed fan-cooled motor on the deck, outside the fan stack and clear of the wet discharge. Its own cowl fan cools it, so blocked vents and a hot terminal box are what to look for.
See also:
Drive shaft
Drive train
Composite tube with flanged couplings and flexible elements at each end, carrying torque from the external motor to the gearbox. Misalignment shows up here first, as vibration.
See also:
Drift eliminator
Fill & media
Blade or cellular type. Strips entrained droplets from the leaving air — the difference between plume, water loss, and deposits on nearby plant.
See also:
Distribution system
Water distribution
Hot water arrives from the process through the main, rises into the header, and spreads across the plan through the laterals. Even flow to every nozzle is what a performance test is really measuring — a blocked lateral shows up as a hot corner.
See also:
Spray nozzle
Water distribution
Fixed-orifice or swirl-vane nozzles on the distribution header. Uniform coverage over the fill is what performance testing actually measures.
See also:
Fill pack
Fill & media
Film or splash fill, in several flute geometries chosen for water quality. The largest single lever on thermal performance — and the first thing to foul, sag or collapse.
See also:
Air inlet
Airflow
The open face the fan draws through. Air enters here, crosses the falling water in the fill, and leaves through the stack as a warm saturated plume — induced draft. Anything that blocks the inlet, or lets discharge recirculate back into it, costs capacity directly.
See also:
Cold water basin
Shell
Collects cooled water and feeds the return line. Silt, scale and corrosion here quietly degrade everything downstream.
See also:
